Comprehensive information relating to the Master Bakers scheme
 
INFORMATION SHEET 16

CALCULATIONS

To Calculate Delivered Energy:

Delivered Energy = Sum of All Below:

To Obtain Energy in kWh:

From

To

Imported From Utility Companies

Electricity

in kWh

Multiply by 1.0

kWh

kWh

Natural Gas

in kWh

See Gas Bill

Gas Oil

in kWh

Multiply by 10.6

litres

kWh

Light Fuel Oil

in kWh

Multiply by 11.2

litres

kWh

Medium Fuel Oil

in kWh

Multiply by 11.3

litres

kWh

Heavy Fuel Oil

in kWh

Multiply by 11.4

litres

kWh

Propane (1)

in kWh

Multiply by 13.89

kg

kWh

Propane (2)

in kWh

Multiply by 7.04

litres

kWh

Butane

in kWh

Multiply by 13.69

kg

kWh

Coal

in kWh

Multiply by 8,500

tonnes

kWh

Anthracite

in kWh

Multiply by 8,236

tonnes

kWh

Coke

in kWh

Multiply by 7,750

tonnes

kWh

Imported Energy Substitute

Liquid Nitrogen (1)

in kWh

Multiply by 440

tonnes

kWh

Liquid Nitrogen (2)

in kWh

Multiply by 0.55

m3

kWh

Liquid CO2 (1)

in kWh

Multiply by 203

tonnes

kWh

Liquid CO2 (2)

in kWh

Multiply by 0.375

m3

kWh

Steam

in kWh

Depends upon Operating Conditions

Imported From Private Energy Sources

Electricity

in kWh

See above

Natural Gas

in kWh

See above

Steam

in kWh

See above

To Calculate Specific Energy Consumption (SEC):

Net Primary Energy = (Total Primary Energy) - (Total Exported Primary Energy) - (CHP Export Adjustment)
   
Note: CHP Export Adjustment is Zero if you do not have a CHP Plant. Please contact helpline for help in calculating the adjustment
   
SEC (Delivered) = Net Delivered Energy (kWh)
  Total Production (tonnes)
   
SEC (Primary) = Net Primary Energy (kWh)
 

Total Production (tonnes)

To Calculate Primary Energy:

Primary Energy = Sum of All Below:

To Give Primary Energy: Multiply Delivered Energy By

Imported From Utility Companies

Electricity

in kWh

2.6

Natural Gas

in kWh

1.0

Gas Oil

in kWh

1.0

Light Fuel Oil

in kWh

1.0

Medium Fuel Oil

in kWh

1.0

Heavy Fuel Oil

in kWh

1.0

Propane

in kWh

1.0

Butane

in kWh

1.0

Coal

in kWh

1.0

Anthracite

in kWh

1.0

Coke

in kWh

1.0

Imported Energy Substitute

Liquid Nitrogen

in kWh

2.6

Liquid CO2

in kWh

2.6

Steam

in kWh

1.0

Imported From Private Energy Sources

Electricity

in kWh

2.6

Natural Gas

in kWh

1.0

Steam

in kWh

1.0

To Calculate Net Carbon Emitted:

Carbon Emitted per Fuel (CEF) = Primary Energy of the Fuel x Fuel Carbon Conversion Factor
   
Note: Carbon Conversion Factors are given in Schedule 2, Paragraph 3.1 of the Underlying Agreement
   
Net Carbon Emitted = Sum of Imported CEF - Sum of Exported CEF - CHP Export Adjustment

To Calculate Specific Carbon Emission:

Specific Carbon = Net Carbon Emitted (kg C)
  Total Production (tonnes)

 

 

 

[CCL Home] [Master Bakers Home] [Calculate] [Guidance]